Andrew 241088-1


*Grounding Kit, 1/2" Attached 2 Hole Lug

BSW PART: 241088-1

241088-1
Standard Grounding Kit for 1/2 in corrugated coaxial cable

Dimensions
Nominal Size 1/2 in
Waveguide Size WR42 | WG20 | R220 | WR51 | WG19 | R180
Bonding Conductor Length 609.6 mm | 24 in
Cable Jacketing Removal Length, maximum 59.1 mm | 2.3 in
Cable Jacketing Removal Length, minimum 55.9 mm | 2.2 in
Compatible Diameter, maximum 16.510 mm | 0.650 in
Compatible Diameter, minimum 15.494 mm | 0.610 in
Electrical Specifications
Current Handling Tested to withstand 100,000 amps peak current surge
Current Handling Test Method MIL-STD-1757
Grounding, Bonding and Shielding Test Method MIL-STD-188-124A
Lightning Protection Test Method IEC 1024-1
General Specifications
Cable Type Corrugated | Elliptical waveguide
Grounding Kit Type Standard Grounding Kits
Color Black
Bonding Conductor Material Copper
Bonding Conductor Wire Size 6 gauge
Bonding Conductor Jacketing Material PE
Grounding Strap Material Copper
Includes Grounding kit | Hardware | Lug | One roll of 2 in PVC tape | One roll of 24 in butyl rubber tape
Lug Attachment Factory attached
Lug Type Two-hole lug
Package Quantity 1
Rivet Material Copper
Weatherproofing Method Butyl and electric tape
Mechanical Specifications
Blowing Rain Test Method MIL-STD-810, Method 506
Corrosion Test Method MIL-STD-1344, Method 1001
Freezing Rain/Icing Test Method MIL-STD-810, Method 521
Humidity Test Method MIL-STD-1344, Method 1002
Immersion Test Method IEC 60529:2001, IP68
Operating Temperature -40 °C to +85 °C (-40 °F to +185 °F)
Storage Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Thread Size 3/8 in
UV Resistance Test Method MIL-STD-810, Method 505
Vibration Test Method MIL-STD-202, Method 214
Packed Dimensions
Height 266.7 mm | 10.5 in
Length 57.2 mm | 2.3 in
Shipping Weight 0.72 kg | 1.58 lb
Width 266.7 mm | 10.5 in

List Price
$32.00
Call for availability
Contact us for your Discounted Price


View ALL Andrew Products