The Burk AC Current Sensor (model #910-093-001) allows measurement of current in AC power lines. Use the AC Current Sensor to monitor incoming AC power, or generator output. The unit provides an analog output for connection to a metering input.
Key Features
• Factory matched and calibrated single piece transducer is more accurate than traditional two-piece field installed solutions.
•" Average Responding" algorithm gives an RMS output on pure sine waves. Perfect for constant speed (linear) loads.
• Jumper-selectable input range reduces inventory and eliminates zero and span pots.
• Ouput is magnetically isolated from the input for safety.
• Insertion loss (voltage drop) is eliminated through isolation.
• UL, cUL, and CE approved
Output Signal:
0-5VDC
Output Limit:
8.2VDC
Accuracy:
1.0% FS
Response Time (10-90% step change):
100ms
Frequency Range:
50-60Hz
Power Supply:
Self-powered
Loading:
1mΩ minimum for rated accuracy. 100KΩ add 1.3% error.
Isolation Voltage: UL listed to 1,270VAC (tested to 5KV).
Input Ranges:
Field-selectable ranges of 10, 20 and 50A
Sensing Aperature:
0.75" (19mm) diameter
Case:
Fixed core, top mounted terminals. UL 94V-0 Flammability rated.