Bing ads convertion tracker Davicom DV-216-1
Bookmark and Share

Davicom DV-216-1


2 RU height - 2 I/O cards (16 metering, 32 status, 32 output relays, 8 audio inputs, 8 RS232

BSW PART: DV-216-1

DV_216_1.JPG
The Davicom System is designed for the Monitoring and Alarm Control of equipment installed at remote transmission sites. Surveillance is accomplished by sampling the analog and digital input signals, while control is obtained through the opening and closing of relay contacts. The system also allows remote audio monitoring of the site via a touch-tone telephone or audio streaming over an IP connection. Multiple Input/Output configurations allow you to choose the appropriate size of Davicom unit.

Main Features and Benefits:
• Easy installation, set-up and operation.
• Reliable proven in the field since 1994.
• Stand-alone units that do not require a computer at the site.
• Very intelligent and simple
• Reduced site maintenance costs
• Reduced overtime thanks to minor alarm muting functions.
• Widest choice of means of communications including secure 128-bit* encrypted IP.
• Redundancy due to Dual-modem ready.
• No moving parts such as hard disk drives or fans.
• Can handle electric fields of over 10 V/m and electrostatic discharges of 12 kV.
• Easy upgrades
• Direct monitoring of site audio via telephone or IP streaming.
• Real-time access to site information from anywhere in the world.
• Increased security at remote sites.
• User-customizable interface
• Single location management of all sites.

Specifications:
• Metering (Analog) Inputs: (16) - Resolution: 12 bits, Bipolar / Differential, 3 selectable ranges: -2.5 to +2.5, -10 to +10 and -20 to +20 VDC, 4-20mA input mode jumper selectable, Impedance > 100 kOhms, True-RMS converter (optional): 60 Hz to 20 kHz.
• Status (Digital) Inputs: (32) -  EIA compatible, Opto-isolated, Impedance > 22 kOhms, Detection levels: -12 to +0.8 VDC (low), +2.4 to +12 VDC (high).
• Audio Inputs: (8) -20 to +10 dBm (300-3000 Hz); Impedance 10 kOhms.
• Line in & MIC in: (2) - PC sound-card standard LINE-IN and MIC-IN connections.
• Outputs (Commands): (32) -  Selectable NO/NC dry contact relays (70 VAC @ 0.4 A, 30 VDC @ 2 A) or open collector (100 mA)
• Auxiliary DC Outputs: (4) - 5 VDC @ 250mA max per I/O board, 12VDC @ 500mA max per I/O board >> Total combined 1500mA max
• Local Access Port: (1) - 115200 bps, DB9 female connector located on front panel; or 115200 bps, USB Type B connector located on front panel.
• Serial Ports for On-Site Ancillary Equipment: (8) - 1200 to 115200 bps, DB9 male connectors located on rear panel.
• Extra Serial Ports for On-Site Ancillary Equipment through USB Hub & Dongles: (8) - 1200 to 115200 bps, DB9 male on USB dongles connected through USB hub.
• Serial Ports for External Modems: (2) - 1200 to 57600 bps, DB9 male connector located on rear panel.
• Extra Ports for External Modems through USB Hub: (4) - USB modems required. Must support Linux CDC drivers.
• Internal Modem: (1) - RJ-11 jack located on rear panel, Voice/Fax/Data, 56 kbps maximum, Fax up to 14400 bps, DTMF interface.
• External USB Storage through USB Hub: (4) - Up to 4 external USB memory devices. FAT32 formatted devices only.
• Real Time Clock (RTC): 3.8 PPM between -10°C and +60°C. Equivalent to 10 seconds per month.
• Power Requirement: 11.5-14.5 VDC, 1.5 A Max.
• Fuse: 250 V, 3 A
• Electric Fields: Tested to 10 V/m
• Electrostatic Discharge (ESD): Tested to 12 kV
• Operating Temperature Range: -40°C to +80°C (-40°F to +176°F )
• Dimensions: 2 RU 19 x 3.5 x 12 in (W x H x D) 48.3 x 8.9 x 30.5 cm
Weight:
• 10 lbs (4.5 kg) dry
• 11 lbs (5 kg) shipping

List Price
$7,595.00
Call For Availability
Contact us for your Discounted Price